4.9 Acc/Dec Pattern Configuration
Acc/Dec gradient level patterns can be configured to enhance and smooth the
inverter’s acceleration and deceleration curves. Linear pattern features a linear
increase or decrease to the output frequency, at a fixed rate. For an S-curve pattern a
smoother and more gradual increase or decrease of output frequency, ideal for lift-
type loads or elevator doors, etc. S-curve gradient level can be adjusted using codes
Ad. 03
–06 in the Advanced group.
Grou
p
Code
Name
Setting
Setting Range
Unit
bA
08
Acc/Dec reference
frequency
0 Max Freq
0
–1
-
Ad
01
Acceleration pattern 0 Linear
0
–1
-
02
Deceleration pattern 1 S-curve
-
03
S-curve acceleration
start point gradient
40
1
–100
%
04
S-curve acceleration
end point gradient
40
1
–100
%
05
S-curve deceleration
start point gradient
40
1
–100
%
06
S-curve deceleration
end point gradient
40
1
–100
%
Acc/Dec Pattern Setting Details
Code and
Features
Description
Ad.03 Acc S
Start
If the acc/dec pattern is set as the S-curve, set the gradient level (slant)
for the acceleration start time. Gradient level is the ratio which gradient
acceleration takes up in the section under 1/2 frequency based on the
1/2 frequency of target frequency.
If the frequency reference and maximum frequency are set at 60 Hz
and Ad.03 is set to 50%, 0
–15 Hz section will conduct curve
acceleration and the 15-30 Hz section will conduct linear acceleration
when the S-curve accelerates up to 30 Hz.
Ad.04 Acc S
End
Set the gradient level for when the operation frequency reaches the
target frequency.
The curve ratio is the ratio that the curve acceleration takes place
within the section above the 1/2 frequency, based on the 1/2 frequency
of the frequency reference.
If the setting is set identical to the Ad.03 Acc S Start example, the 30
–
45 Hz section will conduct linear acceleration. The 45
–60 Hz section
will first conduct curve acceleration then conduct at a constant speed.
Ad.05 Dec S
Start
–
Ad.06 Dec S
Sets the rate of S-curve deceleration. The setup method is the same
as the ratio during acceleration.
Summary of Contents for G100
Page 14: ......
Page 16: ...5 5 7 5 kW 3 Phase ...
Page 32: ...0 4 0 8 kW 1 5 2 2 kW 4 0 kW ...
Page 48: ......
Page 68: ......
Page 81: ......
Page 100: ......
Page 116: ...trips automatic Reset Restart is not attempted and the Fire Mode Count is not increased ...
Page 118: ......
Page 130: ... Terminal connections for 3 wire operation 3 wire operation ...
Page 140: ... PID control block diagram ...
Page 165: ...Code and Features Description Code Description continuous rating ...
Page 170: ......
Page 186: ... Displayed as on the Keypad ...
Page 200: ...provided signal output at 150 36 sec ...
Page 216: ...Code and Features Description delay time delay time ...
Page 219: ......
Page 237: ......
Page 253: ......
Page 295: ......
Page 314: ......
Page 335: ...Manual Revision History Revision History No Date Edition Changes 1 2019 01 First Release ...