SV-iS7 CANopen Manual
28
6.1.2.10
vl velocity Quick Stop (Object: 0x604A)
Index
: 0x604A
Function
: Object which determines Quick Stop time
Unit
: sec
Basic format
: 0.0
Setting range
: 0.0 ~ 600.0 (Setting range differs from parameter setting of inverter.)
As shown in the figure, the deceleration time is determined using the Delta speed and Delta
time. For the safety of the inverter, the delta_speed was fixed to Max speed, and the setting
parameter was removed.