SV-iS7 CANopen Manual
37
7.4.2 COM 51~54 Para Control
This can be set up only when the LS Device Profile is selected in the COM11.
4 parameter addresses are designated and the parameter values transmitted to the Master through RPDO3 is
used. If CiA 402 Velocity Mode is selected, this status is hidden and setting is prohibited.
7.5
Parameter setting for the Lost Command
According to the decision criteria of the Lost Command of the IS7 CANopen, it judges that the Master and Slave
are connected when the NMT status of the CANopen is Operation, and it does not generate Lost Command. That
is, when the NMT State different from Operation is maintained for longer than the time set up in the PR-13, the
inverter turns to Lost Command state. However, the Lost Command can be generated only when one or more of
the frequency command or operation command is set to Fieldbus.
7.5.1 PRT-12 Lost Cmd Mode
None: no action is taken even when the Inverter turns to Lost Command state.
Free-Run: in Lost Command state, the motor turns to Free Run stop and Lost Command Trip is triggered.
Dec: in Lost Command state, the motor turns to trip deceleration stop, and Lost Command Trip is
triggered.
Hold Input: the motor runs at the last speed command, and Lost Command Warning is issued.
Hold Output: the motor runs at the current speed, and Lost Command Warning is issued.
Lost Preset: the motor runs at the speed set up in the PRT-14, and Lost Command Warning is issued.
7.5.2 PRT-13 Lost Cmd Time
While the CANopen is in communication, if the MNT State different from Operation is maintained for the time
longer than the time set up in the PRT-13, the Inverter turns to Lost Command state.
7.5.3 PRT-14 Lost Preset F
If Lost Preset is set up in the Lost Cmd Mode of the PRT-12, and if the Inverter turns to Lost command state, the
inverter drives the motor at the speed set up in the PRT-14.