7. Function List
7-5
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
F29
[Torque
boost in
reverse
direction]
This parameter sets the
amount of torque boost
applied to a motor during
reverse run.
It is set as a percent of Max
output voltage
5
X
F30
[V/F pattern] 0/2
0 {Linear}
0
X
1 {Square}
2 {User V/F}
F31
3)
[User V/F
frequency 1]
0/400
[Hz]
This parameter is active
when F30 – [V/F pattern] is set
to 2 {User V/F}.
It cannot be set above F21
– [Max frequency].
The value of voltage is set
in percent of H70 – [Motor
rated voltage].
The values of the lower-
numbered parameters cannot
be set above those of higher-
numbered.
15.0
X
F32
[User V/F
voltage 1]
0/100
[%]
25
X
F33
[User V/F
frequency 2]
0/400
[Hz]
30.0
X
F34
[User V/F
voltage 2]
0/100
[%]
50
X
F35
[User V/F
frequency 3]
0/400
[Hz]
45.0
X
F36
[User V/F
voltage 3]
0/100
[%]
75
X
F37
[User V/F
frequency 4]
0/400
[Hz]
60.0
X
F38
[User V/F
voltage 4]
0/100
[%]
100
X
F39
[Output
voltage
adjustment]
40/110
[%]
This parameter adjusts the
amount of output voltage.
The set value is the
percentage of input voltage.
100
X
F40
[Energy-
saving level]
0/30 [%]
This parameter decreases
output voltage according to
load status.
0
0
F50
[Electronic
thermal
select]
0/1
This parameter is activated
when the motor is overheated
(time-inverse).
0
0
2) Only displayed when F24 (Freq High/Low limit select) is set to 1.
3): Set F30 to 2 (User V/F) to display this parameter.
Summary of Contents for SV004iC5-1F
Page 8: ......
Page 22: ...3 Wiring 3 6 ...
Page 38: ...5 Programming Keypad 5 14 ...
Page 42: ...6 Basic Operation 6 4 ...
Page 64: ...7 Function List 7 22 ...
Page 74: ...9 Specifications 9 4 ...