7. Function List
7-11
LED
display
Parameter
Name
Min/Max
Range
Description
Factory
defaults
Adjustable
during run
Page
H26
[Number of
Auto
Restart try]
0/10
This parameter sets the
number of restart tries after
a fault occurs.
Auto Restart is
deactivated if the fault
outnumbers the restart tries.
This function is active
when [drv] is set to 1 or 2
{Run/Stop via control
terminal}.
Deactivated during
active protection function
(OHT, LVT, EXT, HWT etc.)
0
O
H27
[Auto
Restart time]
0/60
[sec]
This parameter sets the
time between restart tries.
1.0
O
H30
[Motor type
select]
0.2/2.2
0.2
0.2 kW
-
1)
Automatically
set
X
0.4
0.4 kW
0.75
0.75 kW
1.5
1.5 kW
2.2
2.2 kW
H31
[Number of
motor poles]
2/12
This setting is displayed
via rPM in drive group.
-
X
H32
[Rated slip
frequency]
0/10
[Hz]
×
−
=
120
P
rpm
f
f
r
s
Where,
s
f
= Rated slip frequency
r
f
= Rated frequency
rpm
= Motor nameplate RPM
P
= Number of Motor poles
-
2)
Automatically
set
X
H33
[Motor rated
current]
1.0/20
[A]
Enter motor rated
current on the nameplate.
-
X
H34
[No Load
Motor
Current]
0.1/12
[A]
Enter the current value
detected when the motor is
rotating in rated rpm after
the load connected to the
motor shaft is removed.
Enter the 50% of the
rated current value when it
is difficult to measure H34 -
[No Load Motor Current].
-
X
H36
[Motor
efficiency]
50/100
[%]
Enter the motor efficiency
(see motor nameplate).
-
X