Chapter 7 Diagnosis Function
7-8
7.3 Troubleshooting
This part describes causes and actions on failures and errors that may happen in operating systems. When a user wants to
check out errors and problems in EtherNet/IP I/F Module, the following procedure will help you check out those
malfunctions. When judging whether the module is in abnormal state or not, make sure to take actions in order, using
Troubleshooting. Do not repair and disassemble at your discretion.
7.3.1 Check-out through LED in Communication Module
This check-out is the way of checking out the state of the module to see whether it is defective or not.
1)
Abnormal Operation Display
LED located on the front side of EtherNet/IP I/F Module enables a user to check out.
[Illustration 7.3.1] LED of EtherNet/IP I/F Module
LED Contents
Error Contents
Actions
RUN
Light out after supplying
the module power
1) Check out whether EtherNet/IP Communication Modules has been properly
installed or not
- Check out whether the communication module has been properly installed to
the main unit
2) Consult with Warranty Service Center
I/F
Operation stops when light
is on and off
1) Check out whether main unit and communication modules have been properly
installed
2) Consult with Warranty Service Center
P2P
Light is off during service
for command languages
1) Check out whether command language has been properly entered or not
2) Check out connection has been properly done or not
3) Check out whether Link Enable in Menu is on or not
PADT
Light is off during remote
connection service
1) Check out whether telephone office numbers for remote connection(PADT)
have been properly set up or not
2) Check out whether PADT Program – Remote Connection has been canceled
SVR
Light is off during server
operation
1) Check out whether the connection with client has been properly done
MS
Red light is on and off 1) Check out the basic set-up and supply power again
Red light is on
1) Supply power again
2) Consult with Warranty Service Center
NS
Red light is on and off
1)Check out the device where Timeout happened
Red light is off
1) Set up IP Address again (Find the same IP Address)
ACT
Light is off during normal
communication
1) Check out the transmission or reception parameter
2) Check out whether connection has been properly done
Summary of Contents for XBL-EIPT
Page 53: ...Chapter 5 Installation of Software and communication Parameters 5 18 ...
Page 98: ...Chapter 7 Diagnosis Function 7 11 Figure 7 3 4 FlashArea Log Screen of System Log ...
Page 106: ...Chapter 7 Diagnosis Function 7 19 Fig 7 4 9 Remote 2 connection directly via Ethernet ...
Page 119: ...Appendix A 12 A 3 External Dimension Dimension Unit mm XBL EIPT ...