Chapter 6 Function of CPU Module
6
-
15
6.10 Changing Module during Operation
XGK system enables to change the module during operation. But, as the change of module during operation
may occur the abnormal operation of whole system, special attention should be taken. Just follow the procedure
assigned in this user’s manual.
1) Notices in Using
•
Not allowed to change the base and power module.
•
Some part of communication module (XGL-PMEA, XGL-DMEA) needs the network setting (Sycon used) for
communication.
•
In case of module change, match the joint part of the lower part of base and module correctly before inserting.
If not, it may cause the system shutdown.
2) Module Change Method
There are 2 kinds of module change method.
(1) By using XG5000 “Module Change Wizard” function.
For further information, please refer to XG5000 user’s manual.
(2) By using CPU module switch
(1) Set “Module change switch (M.XCHG)” in front of CPU module as right(ON).
(2) Remove the module. (PS LED is ON)
(3) Setup the new module. (in case of normal module setup, PS LED is OFF)
(4) Check if module operates normally.
(5) Set “Module change switch (M.XCHG)” as left (OFF).
1) When changing the module, shut down the load power for safety.
2) When changing the input module, consider the setting of input image state by using the
forced On/Off.
Notes
When installing the module, it may cause an abnormal operation if the lower connection is not
mounted on the base completely.
Warning