Chapter 7 I/O Module
7-13
7.3.2 16 point Relay Output Module
Relay Output Module
Model
Specification
XGQ-RY2A
Output point
16 point
Insulation method
Relay insulation
Rated load voltage/current
DC24V 2A(resistive load) / AC220V 2A(COS
Ψ
= 1)
Min. load voltage/current
DC5V / 1mA
Max. load voltage/current
AC250V, DC125V
Off leakage current
0.1mA (AC220V, 60Hz)
Max. on/off frequency
3,600times/hr
Surge absorber
None
Mechanical
20 million times or more
Rated load voltage/current 100,000 times or more
AC200V / 1.5A, AC240V / 1A (COS
Ψ
= 0.7) 100,000 times or more
AC200V / 1A, AC240V / 0.5A (COS
Ψ
= 0.35) 100,000 times or more
Service life
Electrical
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100,000 times or more
Off
→
On
10 ms or less
Response
time
On
→
Off
12 ms or less
Common method
16 point / 1COM
Current consumption
500mA (when all points On)
Operation indicator
Output On, LED On
External connection method
18 point terminal block connector (M3 X 6screw)
Weight
0.17kg
Circuit configuration
Terminal
block
Contact
TB1 P0
TB2 P1
TB3 P2
TB4 P3
TB5 P4
TB6 P5
TB7 P6
TB8 P7
TB9 P8
TB10 P9
TB11 PA
TB12 PB
TB13 PC
TB14 PD
TB15 PE
TB16 PF
TB17 COM
TB18 NC
00
0A
0E
02
04
06
08
0C
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
01
03
05
07
09
0B
0D
0F
COM
RY
Internal
circuit
Terminal
block no.
TB1
TB17
TB16