Description

The addressable Thermal Detector 5251EM is based 

on the heat principle and was developed for the indoor 

temperature supervision in a wide range of fi re detec-

tion applications.

When used with a Fire Detection Control Panel Series 

BC216, the detector can operate either as maximum 

heat detector with alarm temperature 58°C (EN 54-5 

Class A1S) or alarm temperature 78°C (EN 54-5 Class 

BS), or as rate-of-rise heat detector with a maximum 

temperature of 58°C (EN 54-5 Class A1R).

The  proven  ADM  loop  technology  with  System  Sen-

sor/200 protocol establishes a permanent communi-

cation between the fi re detection control panel and the 

detector. That ensures a periodical function testing of 

the detector. Fires are safely detected in the control 

panel by continuously analysing the measured values.

The two LEDs with 360° visibility indicate the activated 

condition of the detector. The detector address is se-

lected with two decadic rotary switches, thus allowing 

to change the detector without additional tools.

A detector function test can be conveniently conducted 

using a magnet or a detector test device. The detector 

can be attached to various bases and it can be protec-

ted against theft.

•   ADM loop technology with 

System Sensor/200 protocol

•   For use as maximum heat or

rate-of-rise heat detector

•   Alarm temperature 58°C or 78°C 

software selectable

•   Optional connection of remote 

indicator

•   Function testable with magnet

Reviews: