background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

55100-908_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Specifi cations

Description

The  Manual  Call  Point  55100-908  complies  with  the 

standard EN 54-11/A and is designed for use in ADM 

loops with Apollo/Discovery protocol.

The  detector  is  activated  by  pressing  in  the  pane  of 

plastic.  By  means  of  a  special  key,  the  pane  can  be 

put back to the idle position, thereby resetting the de-

tector.

The two-coloured status LED indicates the activation of 

the detector in red colour and the fault condition in yel-

low colour. The detector address is selected by means 

of a DIL switch. A dual-isolator, which is integrated into 

the detector, disconnects the adjacent loop elements 

fast and safely in case of a short circuit.

The  detector  is  fi tted  into  a  plastic  case  and  can  be 

mounted  on  a  60mm  fl ush-mount  installation  box.  By 

means of the supplied case, surface mounting on a wall 

is also possible.

•   ADM loop technology with

Apollo/Discovery protocol

•   Activation by pressing in the pane of 

plastic

•   Two-coloured LED indicates activation 

and fault

•  Integrated dual-isolator
•   Operating instructions by means of 

standardised symbols

Operating voltage 

Supply through loop voltage

Current consumption 

100µA (quiescent)

Ambient temperature 

-20°C to +60°C (no condensation or icing)

Relative humidity 

max. 95% (no condenstation)

Protection class 

IP24

Dimensions W × H × D

   with surface mount box 

89 × 93 × 59 (mm)

   installation on fl ush-mount installation box 

89 × 93 × 28 (mm)

Colour 

fl ame red, RAL 3000

Weight 

160g

Order number 

245015

Order name 

Manual Call Point/Red/XP95/ISM/Flexi 55100-908