background image

0786–CPD–20361

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

HFM-ADM_DBL_LST_EN_0819.PDF • PAGE 1

A

Building Safety. Building Security.

Description

Specifi cations

The manual call point according to EN 54-11/B is de-

signed for use in ADM loops with System Sensor/200 

protocol  and  is  accommodated  in  a  robust  die-cast 

aluminium case. In comparison with plastic cases, the 

aluminium case proves to be of advantage even after 

years of use, thanks to its resistance to environmental 

impact: It is virtually unbreakable, form stable and hard-

ly changes its colour in sunlight.

A built-in LED optically indicates the activated condition 

of the manual call point. The detector address can be 

set by means of a push-button and the entered address 

is displayed by an LED. The detector is provided with a 

dual-isolator, which disconnects the adjacent loop ele-

ments fast and safely in case of a short circuit.

The hinged door can be opened up to an angle of 180° 

and it is provided with a replaceable pane of glass. If 

the detector has been activated, an integrated locking 

device prevents the closing of the door.

Custom versions with different colours, designs, func-

tions  and  internal  wirings  are  available  on  inquiry.  By 

means of the optional Protection Kit HFM/HM-ZS-IP54, 

the protection class can be increased to IP54.

•   ADM loop technology with

System Sensor/200 protocol

•   Robust die-cast aluminium case
•  LED indicates activation
•  Integrated dual-isolator
•   Operating instructions by means of 

standardised symbols

•   Increase of protection class to IP54 

by using optional protection kit

Operating voltage 

Supply through loop voltage

Current consumption 

300µA (quiescent)

Ambient temperature 

 -20°C to +60°C (continuous operation)

-25°C to +70°C (max. 12 hours)

Protection class 

IP43

Dimensions W × H × D 

125 × 125 × 34 (mm)

Colour 

fl ame red, RAL 3000

Weight 

400g

Approval 

VdS G202035

 

0786-CPD-20361

Order number 

245362

Order name 

Manual Call Point/Red/Anal./SS HFM/3/22/02