Description

The addressable Module 55000-875 serves for the line-

monitored integration of a contact detector, such as a 

manual call point, a sprinkler system contact or a su-

pervising contact, into the bidirectional communication 

on the ADM loop with Apollo/Discovery protocol. Fur-

thermore, it can be used to actuate external devices by 

means of a relay output with a dry change-over contact, 

via the ADM loop.

The address is easily selected by means of a built-in DIL 

switch. Status LEDs indicate the condition of input and 

output. The module has an integrated dual-isolator and 

is fi tted into a plastic case.

•   ADM loop technology with

Apollo/Discovery protocol

•   One line-monitored input and one 

dry relay output 230VAC

•   Setting of module address by means 

of address switch

•  Integrated dual-isolator
•   Status LEDs for input and output

Specifi cations

Operating voltage 

Supply through loop voltage

Current consumption 

approx. 1.25mA (quiescent)

Contact rating 

2A/48VDC or 5A/230VAC

Ambient temperature 

-20°C to +70°C

Dimensions L × W × H 

150 × 90 × 48 (mm)

Colour 

white

Weight 

240g

Order number 

249078

Order name 

Module 1xSurv.In 1xRel.Out-230/Apo 55000-875