Description
With the Detector Zone Extension MGE8-1 the fi re de-
tection control panel Series BC016 can be extended
from 8 to 16 addressable detector zones. Up to 64
detectors (addresses) per detector line can be indivi-
dually identifi ed with the aid of an address module. In
the event of an alarm, the fi re detection control panel
indicates the number of the detector that triggers the
alarm fi rst.
Depending on the type of detector (manual call point,
automatic fi re detector with or without alarm verifi cati-
on, fault message contacts as well as contacts for tech-
nical messages), the function of the detector zone can
be set separately for each detector line. Each input of
the Detector Zone Extension is protected against over-
voltage and thus provides high system stability.
• Extends fi re detection control panels
Series BC016 to 16 detector lines in
addressable conventional technology
• Individual detector addressing with
optional address module
• Individual setting of detector zone
function
• Lines monitored for wire breakage,
short circuit, and short to earth
Specifi cations
Current consumption at 24V
typ. 32mA (8 zones terminated, without detectors)
Line voltage
typ. 20.0V
Line current
typ. 3.8mA
End-of-line resistance
5.6k
Ω
or 3,3k
Ω
(depending on setup)
Line resistance
max. 50
Ω
per core
Ambient temperature
-5°C to +50°C
Dimensions L × W × H
100 × 65 × 15 (mm)
Weight
80g
Part No.
210110
Order name
Detector Zone Extension MGE8-1