background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

RB-10004_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

Specifi cations

The  Detector  Relay  Base  RB-10004  with  integrated 

relay output is designed for the easy connection of au-

tomatic detectors Series ORBIS. Due to its robust multi-

wire screw terminals, the detectors can be wired with 

ease, thus achieving a secure and durable connection.

In addition, a relay output with a dry change-over contact 

is integrated into the detector base. The relay output is 

activated through the alarm activation of the inserted 

detector and remains active until the alarm is reset on 

the fi re detection control panel.

The base has been designed for surface mounting in 

dry rooms. For special applications a range of acces-

sories (for moist room, false ceiling or fl ush installation) 

is available. 

A  mechanical  theft  protection  of  the  detector  can 

 optionally be activated at the detector base.

Operating voltage 

Supply through the detector line voltage

Current consumption 

7mA (active)

Contact rating 

1A at 30VDC

Ambient temperature 

- 40°C to +70°C

Relative humidity 

10 – 98% (no condensation)

Dimensions ø × H 

100 × 24 (mm)

Colour 

white

Weight 

80g

Order number 

246041

Order name 

Detector Relay Base/Conv./ORBIS/Apo RB-10004

•   Suitable for automatic detectors in 

conventional technology

•   Relay output with dry change-over 

contact

•   Screw terminals for secure 

connection of multiple wires

•   Mechanical theft protection can be 

activated