Top climate system
with LUBING Touch Controller
Copyright © Lubing System - All rights reserved
37
Tank monitoring
Only switch on when the pump is supplied by a buffer tank!
When tank monitoring is switched on, the system only starts
if a signal from the float switch in the tank is present at the cor-
responding input of the controller (tank sufficiently filled). If the
level in the tank is too low, the system stops and an info mes-sage
appears on the display. Press OK to hide this message. The alarm
relay is only switched as long as the float switch gives no signal. If
the level was too low for only a short time, this is also shown as an
info message on the display and can be confirmed with OK
Tank waiting time
If the tank was not sufficiently filled, the pump will not start up again
until after the tank waiting time if the float switch signal is present.
Running mode *
You can select between “auto intern” and “auto extern”.
“auto intern”:
when automatic mode is switched on, the
temperature and humidity sensors are queried to determine the
cooling requirement.
“auto extern”:
the system only reacts to commands from a
connected climate computer.
Active boxes **
With the controller versions LCM, the number of actually required
sections is set. Each connected IO card allows 8 sections.
A maximum of 4 additional IO cards can be connected. A total of
40 sections can theoretically be controlled.
The numbering of the sections is fixed for each IO-Card
(IO-Card1 = 1-8; IO-Card 2 = 9-16; ...).
Sensor parameter *
In this submenu the spectrum of the sensor signals can be selected.
If necessary, offset values can also be set to correct the displayed
values. If, for example, the displayed temperature is 1.0°C too low,
then the offset is set to +1.0°C.
Clamping plan
In this submenu, the status of the inputs and outputs on the
installed boards can be displayed.
In addition, a “Manual mode” (password protected) offers the
possibility to switch individual outputs manually.
Display settings
Various display settings can be made (e.g. display brightness,
dimming settings).
System info
Displays the installed software version.
CAN info
Logging the errors of the CAN bus.
Software update
It is possible to install a new software version from a MicroSD card
(password protected; password 1949).
Backup
You can read out all settings (password 1949).
Restore
If a suitable backup is available on the MicroSD card, the settings
saved here can be restored.
Restart system
When this menu item is selected, the system reboots.
Note:
if additional CAN components are connected, the controller
must be restarted (otherwise the components will not be
recognized).
Standard setting
All values will be set back to standard default values.