Remote 3hr Emergency Pack
Installation & Operating Instructions
LED3EP80
SL
N
L
LED Driver Power INPUT (1)
Connect to
INPUT for LED
LUMINAIRE (3)
Indicator LED (4)
Battery Connector (5)
Mains
input (6)
Connect to Output from LED Driver (2)
INSTALLATION – NON DIMMING
Turn OFF power supply, ensure all required equipment and tools are present.
The Emergency Pack is supplied pre-wired for easy connection to luminaires and drivers. 5 connections need to be made:
Luminaire Ref / Location:
....................
In case of difficulty, contact the installation engineers:-
Tel: .............................
Full recharge time 24 hours
Duration 3 hours
Lamp type - LED
ROUTINE TEST RECORD
Year 1
Year 2
Year 3
Year 4
Year 5
Monthly test
Signed
Date
Signed
Date
Signed
Date
Signed
Date
Signed
Date
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
3 Hour
CONNECTING THE DRIVER (1 & 2)
EMERGENCY LIGHTING TESTING
Months 1 to 11 inclusive – Function test, interrupt the permanent/unswitched supply and check the luminaire operates
in emergency mode at reduced output
Month 12 (Annual) – As months 1 to 11 but for a full 3 hour duration
WARRANTY
Products are protected by warranty for a period of 3 year warranty, from date of purchase against defects in material and
workmanship (unless otherwise stated). Should a product fail to perform as described within the warranty period it will be repaired
or replaced with the same or equivalent product by Luceco, free of charge provided that you: (1) return the product to us with
shipping charge prepaid, (2) provide us with proof of the original date of purchase and (3) quote our return authorization number.
Repaired or replaced products will be returned to you with shipping charges prepaid. Replacement products may be refurbished
or contain refurbished materials. If in our sole discretion, we are unable to repair or replace a defective product, we will refund the
purchase price of the product.
This warranty will not apply if in our judgment, the product fails due to damage in shipment, handling, storage, accident, abuse or
misuse, or if it has been used in a manner not conforming to our product instructions, has been modified in any way, or has any
serial number removed or defaced. Repair or attempted repair will void this warranty. Our maximum liability under the terms of this
warranty is limited to the purchase price of the product covered by the warranty.
The warranty is given under English Law. If any part of this warranty is deemed unenforceable (including any provision in which we
exclude our liability to you) the enforceability of any other parts of the warranty will not be affected. These terms do not reduce your
statutory rights.
THESE TERMS AND CONDITIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE
For further details, terms and conditions and online registration please see
www.luceco.uk
Page 4
Page 1
Tech Help Line
UK -
0845 194 7584
Non UK -
+44 (0)1952 238 100
Supplied by
BG Electrical Ltd
Stafford Park 1 TF3 3BD ENGLAND
Visit our website at
www.luceco.uk
Luceco is a registered trade mark of Nexus Industries Ltd.
Tech Help Line
UK -
0845 194 7584
Non UK -
+44 (0)1952 238 100
Supplied by
BG Electrical Ltd
Stafford Park 1 TF3 3BD ENGLAND
Visit our website at
www.luceco.uk
Luceco is a registered trade mark of Nexus Industries Ltd.
LUMINAIRE INPUT (3)
Connect the lead from emergency pack to the connector on luminaire.
Align arrows, push together and twist to lock.
INDICATOR LED (4)
Drill a 18mm hole close to the installation location of the luminaire. Feed
the indicator cable through the cut out, insert into the housing then push
both into the ceiling until secure.
BATTERY (5)
Push the battery connector together, ensuring correct polarity.
DO NOT FORCE PLUG.
NOTE
- the luminare may illuminate due to
any stored battery charge.
Due to ongoing product improvements, some emergency packs
may require use of the included adaptors to connect to your Luceco
luminaires. Use supplied adaptors to Connection 2 and 3, as required to
connect to your Luceco luminaire.
The emergency pack is supplied pre-wired for connection to the LED
driver supplied with the luminaire. Use the L/N cable from the emergency
pack (1) as the input for the LED driver, and connect the pre-wired
connector from output of the driver to input for emergency pack (2).
Remove Safety covers before installation.
MAINS INPUT (6)
The emergency pack requires a permanent, switched live and neutral. Earth
is not required as the case is Class 2, but provision has been given for a loop
through for earth. Connect to 4 way connection block as per labelled.
PART CODE:
LED3EP80