background image

Remote 3hr Emergency Pack

Installation & Operating Instructions

LED3EP80

SL

N

L

LED Driver Power INPUT (1) 

Connect to 

INPUT for LED 

LUMINAIRE (3)

Indicator LED (4)

Battery Connector (5)

Mains 

input (6)

Connect to Output from LED Driver (2)

INSTALLATION – NON DIMMING

Turn OFF power supply, ensure all required equipment and tools are present.

The Emergency Pack is supplied pre-wired for easy connection to luminaires and drivers. 5 connections need to be made:

Luminaire Ref / Location:

  ....................

In case of difficulty, contact the installation engineers:- 

Tel: .............................

Full recharge time 24 hours

Duration 3 hours

Lamp type - LED

ROUTINE TEST RECORD

Year 1

Year 2

Year 3

Year 4

Year 5

Monthly test

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

Functional

3 Hour

CONNECTING THE DRIVER (1 & 2)

EMERGENCY LIGHTING TESTING

Months 1 to 11 inclusive – Function test, interrupt the permanent/unswitched supply and check the luminaire operates 

in emergency mode at reduced output

Month 12 (Annual) – As months 1 to 11 but for a full 3 hour duration

WARRANTY

   

 

Products are protected by warranty for a period of 3 year warranty, from date of purchase against defects in material and 

workmanship (unless otherwise stated). Should a product fail to perform as described within the warranty period it will be repaired 

or replaced with the same or equivalent product by Luceco, free of charge provided that you: (1) return the product to us with 

shipping charge prepaid, (2) provide us with proof of the original date of purchase and (3) quote our return authorization number.

Repaired or replaced products will be returned to you with shipping charges prepaid. Replacement products may be refurbished 

or contain refurbished materials. If in our sole discretion, we are unable to repair or replace a defective product, we will refund the 

purchase price of the product.

This warranty will not apply if in our judgment, the product fails due to damage in shipment, handling, storage, accident, abuse or 

misuse, or if it has been used in a manner not conforming to our product instructions, has been modified in any way, or has any 

serial number removed or defaced. Repair or attempted repair will void this warranty. Our maximum liability under the terms of this 

warranty is limited to the purchase price of the product covered by the warranty.

The warranty is given under English Law. If any part of this warranty is deemed unenforceable (including any provision in which we 

exclude our liability to you) the enforceability of any other parts of the warranty will not be affected. These terms do not reduce your 

statutory rights.

THESE TERMS AND CONDITIONS ARE SUBJECT TO CHANGE WITHOUT PRIOR NOTICE

For further details, terms and conditions and online registration please see

 www.luceco.uk

Page 4

Page 1

Tech Help Line

UK -

 0845 194 7584

Non UK -

 +44 (0)1952 238 100

Supplied by

BG Electrical Ltd

Stafford Park 1 TF3 3BD ENGLAND

Visit our website at

www.luceco.uk

Luceco is a registered trade mark of Nexus Industries Ltd.

Tech Help Line

UK -

 0845 194 7584

Non UK -

 +44 (0)1952 238 100

Supplied by

BG Electrical Ltd

Stafford Park 1 TF3 3BD ENGLAND

Visit our website at

www.luceco.uk

Luceco is a registered trade mark of Nexus Industries Ltd.

LUMINAIRE INPUT (3)

Connect the lead from emergency pack to the connector on luminaire. 

Align arrows, push together and twist to lock.

INDICATOR LED (4)

Drill a 18mm hole close to the installation location of the luminaire. Feed 

the indicator cable through the cut out, insert into the housing then push 

both into the ceiling until secure.

BATTERY (5)

Push the battery connector together, ensuring correct polarity.  

DO NOT FORCE PLUG

NOTE 

- the luminare may illuminate due to  

any stored battery charge.

Due to ongoing product improvements, some emergency packs 

may require use of the included adaptors to connect to your Luceco 

luminaires. Use supplied adaptors to Connection 2 and 3, as required to 

connect to your Luceco luminaire.

The emergency pack is supplied pre-wired for connection to the LED 

driver supplied with the luminaire. Use the L/N cable from the emergency 

pack (1) as the input for the LED driver, and connect the pre-wired 

connector from output of the driver to input for emergency pack (2). 

Remove Safety covers before installation.

MAINS INPUT (6)

The emergency pack requires a permanent, switched live and neutral. Earth 

is not required as the case is Class 2, but provision has been given for a loop 

through for earth. Connect to 4 way connection block as per labelled.