Issue 5 November 2000
363-206-208
Equipment and Rear Access Cabling for the DDM-2000 OC-12 Multiplexer
Lucent Technologies - Proprietary
See Notice on first page
Table 2-12
Miscellaneous Discrete Telemetry Connections (RT)
Remote Terminal (All Releases)
Remote Terminal Additional
Environmental Inputs (Release 5 only)
Name
Desig.
Conn.
Name
Desig.
Conn.
Term
Color
Minor Alarm
Power Minor Alarm
Fan Control
Input - Common
MN
PMNT-IN
FAN-CTL
-48RET
J68
Env. Input - #20
Input - Common
TLMI-20
TLMI-C
J67
2
9
25
18
O-W
BR-R
BK-O
W-S
Env. Input - #1
Env. Input - #2
Env. Input - #3
Env. Input - #4
TLMI-1
TLMI-2
TLMI-3
TLMI-4
22
21
20
19
R-BR
R-G
R-O
R-BL
Env. Input - #5
Env. Input - #6
Env. Input - #7
Env. Input - #8
TLMI-5
TLMI-6
TLMI-7
TLMI-8
17
16
15
14
W-BR
W-G
W-O
W-BL
Env. Input - #9
Env. Input - #10
Env. Input - #11
Env. Input - #12
TLMI-9
TLMI-10
TLMI-11
TLMI-12
Env. Input - #16
Env. Input - #17
TLMI-16
TLMI-17
8
7
6
5
G-R
O-R
BL-R
S-W
Env. Input - #13
Env. Input - #14
Output - Common
Env. Output - #1
TLMI-13
TLMI-14
TLMO-C
TLMO-1
Env. Input - #18
Env. Input - #19
TLMI-18
TLMI-19
4
3
24
23
BR-W
G-W
BK-BL
R-S
Env. Output - #2
Env. Output - #3
Env. Output - #4
No Connection
TLMO-2
TLMO-3
TLMO-4
NC
Env. Input - #21
TLMI-21
12
11
10
1
O-BK
BL-BK
S-R
BL-W
Table 2-12 Notes:
1. The designation “NC” means no connection.
2. Inputs to the minor alarm and power minor alarm connections are normally derived from the -48 volt
alarm outputs of a SLC
®
Series 5 Carrier System power shelf. An external ground must be connected to
Output-Common to access the alarm. Refer to Figure 2-18 on page 2-65 (Releases 1, 2 and 3) or Figure
2-20 on page 2-67 (Releases 5 and 7).
3. The external inputs to the miscellaneous discretes are a contact closure and are connected to the
DDM-2000 OC-12 by two leads (wires). For each of the miscellaneous inputs 1 through 15 that are being
used, connect one lead to input-common (-48RET) and the other lead to the appropriate alarm designa-
tion (TLMI-X). Refer to Figure 2-18 on page 2-65 (Releases 1, 2 and 3) or Figure 2-20 on page 2-67
(Releases 5 and 7).
4. For each output, connect one lead to output-common and the other lead to the appropriate alarm desig-
nation