Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-403
Issue 4 February 1997
Product Description 2 - 9
ECS DC
Distribution
Panel
Both circuit breaker and fuse protected distribution panels are
available with the ECS Battery Plant. They are orderable as
Group 20 and Group 43, respectively. An alarm connection is
provided with each panel to indicate an open fuse or tripped
circuit breaker and is transmitted to the ECS Controller as a
Major Fuse Alarm, MJF (FAJ).
Circuit Breaker Panel (Group 20)
Distribution to the +24-volt loads is provided with the
ED83182-30 G7 circuit breaker panel. This panel
accommodates up to eighteen 10- to 100-ampere circuit
breakers. A hinged front cover panel allows easy access to the
breakers for connecting load leads or adding circuit breakers.
When dc-dc converters are required, the first four mounting
positions should be reserved for 45-ampere circuit breakers (one
for each converter). Figure 2-3 shows the circuit breaker panel
and Table 2-B describes the circuit breaker options and ordering
information.
Table 2-B: H569-403, Group 20 Lineage
®
2000
ECS Battery Plant Breaker Panel
Circuit breakers operate and provide an alarm during
electrical or manual trip. The Group 20 panel contains 18
positions for circuit breakers. The panel bus bar is sized for
600-ampere capacity.
Circuit Breaker Specifications
Capacity (Amps)
Type Heinemann
Order
Information
H569-403, G20*
10
20
30
45
60
100
KS22010
G-AA
G-AB
G-AC
G-AD
G-AE
G-AF
*
One breaker provided per lettered group. Specify breaker positions 1 to
18, left to right.