3 - 22 Engineering, Planning, and Ordering
Issue 4 February 1997
Low-Voltage
Disconnect/
Reconnect
Feature
Low-voltage BATTERY disconnect/reconnect is available as an
option on the ECS plant. For this feature, two disconnect levels
are available: 20.25 and 21.25 volts. The tolerance on disconnect
levels is +/-0.5 volts. Based on the discussion in paragraphs
“Battery Sizing” and “Battery Voltage,” fill in the following
information.
Is Low-Voltage BATTERY Disconnect/Reconnect required?
_____(yes or no)
If yes, specify the disconnect level _____(20.25 or 21.25)
Controller
Options
The engineering of the ECS controller features involves
orderable circuit packs and DIP switch settings.
Circuit Packs: Circuit pack options for the ECS controller are
presented on the H569-403 battery plant drawing. Refer to that
drawing and to the Controller manual for more information on
the availability of optional circuit packs.
DIP Switch Settings: Certain controller features must be set
during the installation process if requirements differ from the
standard factory settings. The engineering process must provide
Table 3-G: Minimum Wire Gauge (Ampacity) - All Strings
String Number
Minimum Wire Gauge
Selected Wire Gauge
1
2
3
4
5
6