Notes:
1. Slotted machine screws should be pan-head type.
2. Slotted machine and hex cap screws should be SAE Grade
2 steel or equivalent.
3. Socket cap screws should have 100,000 psi minimum
tensile strength.
4. Steel flat washers should be furnished under heads of
socket cap screws.
5. Ferrous screws and washers should have a corrosion
protective finish.
6. Locking means is required only for connections subject to
vibration. Belleville-type washers or jam nuts are the
preferred means.
7. For less than 1/4 inch thick tapped copper bars, use No.8,
No. 10, or 1/4 inch machine screws to minimize applicable
torque. When larger size screws are required, provide
captive-type steel nuts or reduce torque.
8. Torque recommendations are also suitable for all
non-ferrous fasteners, except aluminum.
9. Where application permits, hex cap screws should be used.
Table 4-A: Minimum Torque for All Electrical Connections
(e.g., Bus Bars)
Screw Size
Torques - Lb-In or (Lb-Ft
Wire Connectors
Mechanical
Connectors
8-32
10-24
1/4-20
5/16-18
3/8-16
7/16-14
1/2-13
5/8 -11
3/4-10
15
21
50
100
180
280
(42)
(71)
(125)
19
27
65
135
240
385
(49)
(97)
(172)