Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-416
Issue 2 August 1996
Product Description 2 - 1
2
Product Description
Plant
Specifications
Table 2-A: Lineage
®
2000 Battery Plant Specifications (Model H569-416)
Input Voltage
180-264 Vac (208/220/240 Vac nominal)
Input Frequency
47-63 Hz (50/60 Hz nominal)
Operating Voltage
40-60 Vdc (48 Vdc nominal)
Float Voltage
47-58.5 Vdc (48 Vdc nominal)
Plant Current Rating
600 amperes
Plant Shunt
1200 amperes maximum at 50 millivolts
LVD/R Voltage Settings
40.5 or 42.5 Vdc
Controller
Basic: 113B
Microprocessor option circuit pack
Datalogger circuit pack
-48 Volt Distribution
3 panels accommodate up to (21) KS23616 circuit
breakers each
Rectifier Shelf Assembly
Complement: 4 maximum, each mounts 3 rectifiers
Rectifiers
Type: Lineage
®
2000 364A2
Rating: -48 Vdc nominal, 50 amperes
Complement: 12 maximum