Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-416
2 - 6 Product Description
Issue 2 August 1996
design of the rectifiers reduces installation time to minutes,
permitting easy growth and maintenance without service
interruption.
The Lineage
®
2000 SR Series 50 ampere rectifiers operate over
208/240 Vac 50/60 Hz nominal single phase input range without
any necessary tap changes. A power factor correction circuit
incorporated in the design insures a power factor of 90 percent
or greater for loads above 50 percent of the full load rating. The
rectifiers provide the ECS controller with a full complement of
status and alarm signals. The SR Series 50 ampere rectifier is
both UL recognized and CSA certified.
The rectifier status and alarm signals, ac input, and dc output are
all connectorized. The rectifiers plug into a rectifier shelf
assembly that accommodates a maximum of three individual 50
ampere rectifiers. The ECS plant can be equipped with a total of
four rectifier shelf assemblies for a total capacity of 12 SR Series
50 ampere rectifiers. (See the Lineage
®
2000 SR Series rectifier
product manual for additional information.)
Controller
The ECS controller performs the centralized monitoring, control
and reporting functions for the ECS battery plant. The basic ECS
controller can monitor and control up to 12 rectifiers. It also
provides a single interface point for power alarm and status
reporting.
Two optional expansion circuit packs are available to upgrade
the ECS controller: a microcomputer board equipped with a
powerful 16-bit microprocessor, and a datalogger board. The
microcomputer board adds sophisticated firmware features such
as remote communications, alarm history, and statistics. The
datalogger board may be used in conjunction with the
microcomputer option to provide general purpose ac and dc,
voltage and current monitoring and control. (See the ECS
controller manual for further information.)
Batteries
The ECS Model H569-416 battery plant is compatible with
batteries with a short-circuit current rating less than 7000
amperes. For appropriate system loads and reserve times,
selection of the VR Series battery enables one to maximize space
efficiency and fully realize the benefits of front access, modular
growth, ease of installation and maintenance offered by the ECS
battery plant system design.