Lucent Technologies Lineage
®
2000 ECS Battery Plant H569-416
Issue 2 August 1996
Engineering, Planning & Ordering 3 - 23
Low-Voltage
Disconnect/
Reconnect
Feature
Low-voltage BATTERY disconnect/reconnect is available as an
option on the ECS plant. For this feature, two disconnect levels
are available: 40.5 and 42.5 volts. The tolerance on disconnect
levels is +/-0.5 volts. Based on the discussion in paragraph
“Battery Plant Voltage,” fill in the following information.
Is Low-Voltage BATTERY Disconnect/Reconnect required?
_____(yes or no)
If yes, specify the disconnect level _____(40.5 or 42.5)
Controller
Options
The engineering of the ECS controller features involves
orderable circuit packs and field-movable jumper straps.
Circuit Packs: Circuit pack options for the ECS controller are
presented on the H569-416 battery plant drawing. Refer to that
drawing and to the Controller manual for more information on
the availability of optional circuit packs.
Jumper Straps: If requirements differ from the standard
factory settings, certain controller features must be set during the
installation process. The engineering process must provide the
Table 3-G: Minimum Wire Gauge (Ampacity) - All Strings
String Number
Minimum Wire Gauge
Selected Wire Gauge
1
2
3
4
5
6