Lucent Technologies Supplemental Battery Stand J85504D-1 List 16
Issue 2 September 2000
Installation Guidelines and Preparations 5 - 9
Class B Stranded
Cables Lugs
Class I Stranded
Cables Lugs
Table 5-E: KS24194 Class “B” Stranded Conductor Information
Wire
Size
AWG
or
KCMIL
Area
(Circ
Mils)
(NOM)
Current
Max.
DC Res.
Ohms/
1000 ft.
@20C
Number
of
Strands
Dia. of
Strand
Const.*
Avg.
Ins.
Thick
(in.)
Diameter
Weight/
1000 ft.
(lb.)
Max.
Ship
Length
Per
Reel
Capacity
AMPS
(see
Notes)
Cond
Dia.
(in.)
List 3
List 3
2/0
133100
195
0.419
0.084
19
0.405
0.080
0.622
534
1500
4/0
211600
260
0.528
0.052
19
0.512
0.080
0.730
806
1000
350
350000
350
0.681
0.032
37
0.661
0.095
0.922
1301
700
500
500000
430
0.813
0.022
37
0.789
0.095
1.052
1804
500
750
750000
535
0.998
0.0148
61
0.968
0.110
1.265
2669
350
Note: Minimum bend radius is equal to 5X the overall wire diameter.
*Minimum diameter compressed stranded construction.
Table 5-F: KS24194 Class “I” Stranded Conductor Information
Wire
Size
AWG
or
KCMIL
Area
(Circ
Mils)
(NOM)
Current
Max. DC
Res.
Ohms/M
@20C
Strand
Construction
Number
of
Strands
Avg.
Ins.
Thick
(in.)
Diameters
(in.)
Weight/
1000 ft.
(lb.)
Max.
Ship
Length
Per
Reel
Capacity
AMPS
(see
Notes)
Cond
Dia.
(in.)
List 2
List 2
4/0
211600
260
0.613
0.0546
19x28
532
0.080
0.800
835
1000
350
350000
350
0.800
0.0334
19x45
855
0.095
0.960
1337
700
500
500000
430
0.941
0.0234
37x33
1221
0.095
1.170
1830
500
750
750000
535
1.100
0.0157
37X50
1850
0.110
1.340
2734
350
Note: Minimum bend radius is equal to 5X the overall wire diameter.
*Minimum diameter compressed stranded construction.