Lucent Technologies Supplemental Battery Stand J85504D-1 List 16
6 - 4 Installation Procedures
Issue 2 September 2000
Anchoring
Battery Stand
1. Position battery stand over anchor holes or bolts. Some anchor
types require being inserted into the holes prior to positioning the
equipment to be anchored. See Figures 5-2 through 5-6 for anchor
hardware assembly.
2. Tighten the anchor bolt to the torque value specified for the
anchor. See Table 5-B, Anchor Bolt Specifications.
3. Connect the framework ground pigtail (provided with the battery
stand) to the building ground. The framework ground is provided
loose with the battery stand and should be assembled onto one of
the four non-painted ground connection points that are provided
on the stand. This cable is provided with additional lugs and c-tap
for connections to the building ground. Additional hardware may
be discarded.
4. BEFORE PROCEEDING BE SURE THAT ALL DISCONNECT
SWITCHES ARE SET TO THE OFF (DOWN) POSITION.
5. Connect the stand to the plant distribution (bus work). (see “plant
connection).
6. Remove battery retainer bars and position to the side for battery
installation. Do not cut wire ties securing retainer bars to
disconnect switch wiring.
Installing
Batteries
1. Before proceeding with the installation of the batteries, review or
determine the arrangement of the batteries for the application.
Also review the batteries Pre-Service Checking and Charging
instructions. All batteries should be fully charged before being put
into service
2. In applications using batteries other than the 12IR125 series of
batteries the spacer rods provided with the stand should be
removed and replaced by spacers ordered for the batteries to be
used in your application. The spacer rods may be removed by
sliding through the holes in the top of the battery stand and should
be removed before mounting any equipment on top of the stand.
3. For Hawker C11 batteries install the battery adapter kit (comcode
848466900). The kit contains: (1) rear mounted spacer, (7) battery
spacers, and (4) battery inter-connection bus bars. The rear
mounted spacer mounts into slots in the rear of each battery shelf.
The battery spacers should be positioned between each of the
batteries and on each end of the string. Connect the