Lucent Technologies Supplemental Battery Stand J85504D-1 List 16
5 - 16 Installation Guidelines and Preparations
Issue 2 September 2000
Table 5-I: Electrical Characteristics
Total Clearing I
2
t
The total clearing I
2
t at rated voltage
and at power factor of 15% are given in
Table 5-H. For other voltages, the
clearing I
2
t is found by multiplying by
correction factor K, given as a function
of applied working voltage E
g
(RMS).
Arc Voltage
This curve gives the peak arc voltage
U
L
, which may appear across the fuse
during its operation as a function of the
applied working voltage E
g
(RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor K
p
is given as a function of the RMS load
current I
b
in % of the rated current.