Lucent Technologies Lineage 2000® Battery Distribution Fuse Bay (BDFB)
Issue 4 March 1998
Product Description 3 - 15
cable rack mounting hardware. List K2 provides a bus bar, the
connecting bus bar and insulating standoffs for stacking
additional tiers as required. List K3 provides the ED83019-50
G1 bus bar assembly, which has a 1200 ampere current rating.
Figure 3-12 shows the arbitrary numbering assignment and hole
pattern for the discharge return bus bar for List K3.
Recommended terminal lugs for terminating to the external
discharge return bus bar are listed in Table 3-C. The engineer
must furnish all mounting hardware per Table 3-D.
Table 3-A: Recommended Double Hole Terminal Lugs
For Terminating Input Battery And Return Cables (350 KCMIL Maximum)
KS-24194 L3
KS-24194 L2
WP-91412 List
Comcode
Bolt Size
Centers
Die
Die Code
2/0
1/0
57
405348236
0.375
1.00
Black
45
-
2/0
77
406021725
0.375
1.00
Orange
50
4/0
-
59
405348251
0.375
1.00
Purple
54
-
4/0
27
405347923
0.375
1.00
Yellow
62
350
-
61
405348277
0.375
1.00
Red
71
-
350
183
407890748
0.375
1.00
None
80
Table 3-B: Recommended Double Hole Terminal Lugs
For Terminating To List 20 Discharge Return Bus
KS-5482 Wire KS-20921 Wire WP-91412 List
Comcode
Bolt Size
Centers
Die
Die Code
8
8
75
406021626
0.250
0.62
Red
21
6
6
3
405347519
0.250
0.62
Blue
24
4
4
5
405347576
0.250
0.62
Grey
29
2
-
54
405348202
0.250
0.62
Brown
33
-
2
8
405347683
0.250
0.62
Green
37