Lucent Technologies Lineage 2000® Battery Distribution Fuse Bay (BDFB)
Issue 4 March 1998
Installation 4 - 1
4
Installation
Installation
Material
Provided
•
Frame ground mounting hardware (1/4 inch)
•
Battery and battery return lead mounting hardware (3/8
inch)
•
Load lead mounting hardware (1/4 inch)
•
Load lead return mounting hardware to internal discharge
return bus (1/4 inch)
Installation
Material
Required But
Not Provided
•
Input and output cable and terminal lugs
•
Material handling equipment to unload BDFB at site,
remove from shipping container and set in final position
•
Lifting eye bolts, (4) 5/8-11 threaded holes provided
•
Floor mounting hardware
•
Drill to bore hole for floor anchors
•
Cable rack and associated hardware
•
Common electrician's hand tools, including jeweler's
screwdriver, electrical tape, wire cutters and strippers, 6
AWG to 350 KCMIL
•
Proper crimping tools and dies for connectors. The
connectors specified in this section are WP-91412 and may
be installed with compression tools made by Thomas &
Betts using color-coded dies
•
Common mechanic's hand tools, including flat blade
screwdriver, socket and torque wrenches for 1/4 inch and 3/
8 inch blts, crowbar for uncrating and a small soldering iron
•
All WP-92461 and GMT type load fuses
•
Alarm fuses for cartridge type fuse holders, 18/100 amp
GMT alarm fuse, comcode 402328926
•
Mounting hardware for connecting load return leads to
external discharge return bus
•
Central office and frame ground lugs