Lucent Technologies J85568E-1 Secondary DC Mini-Distribution Bay
Issue 4 January 1999
Installation 5 - 11
Table 5-A: DIP Switch Settings and Alarm Connections
for Generating Frame Alarms
Closure on Alarm (FAJ: C and NO Contacts; PWR Loss: C and NC Contacts)
Alarm Type
DIP Switch Setting
Alarm
Connection
P201
P204
Power Loss
Fuse or Circuit Breaker Alarm (Audible)
Fuse or Circuit Breaker Alarm (Visual)
Fuse or Circuit Breaker Alarm (Remote)
Close Positions 1 and 2 on SW1, SW3, and SW5
Close Positions 4 and 6 on SW1, SW3, and SW5
Close Positions 1 and 3 on SW2, SW4, and SW6
Close Positions 4 and 6 on SW2, SW4, and SW6
pin 1
pin 4
pin 7
pin 10
pin 2
pin 6
pin 9
pin 12
Open on Alarm (FAJ: C and NC Contacts; PWR Loss: C and NO Contacts)
Alarm Type
DIP Switch Setting
Alarm
Connection
P201
P204
Power Loss
Fuse or Circuit Breaker Alarm (Audible)
Fuse or Circuit Breaker Alarm (Visual)
Fuse or Circuit Breaker Alarm (Remote)
Close Position 3 on SW1, SW3, and SW5
Close Position 5 on SW1, SW3, and SW5
Close Position 2 on SW2, SW4, and SW6
Close Position 5 on SW2, SW4, and SW6
pin 1
pin 4
pin 7
pin 10
pin 3
pin 5
pin 8
pin 11
Figure 5-6: Alarm Termination Board