The U-bracket (connection between return and ground) has to be
removed, if the return wire is only grounded at the external
battery (BDFB) source (e.g. valid for the USA domestic market);
see also section
Routing
In case of ...
then ...
top access
route the cables (item 1) directly into
the PDP.
bottom access
route the cables (item 1) via the right
rear side of the rack frame into the PDP
(see figure below).
Figure 4-3 Routing the power input cables
Top access
Bottom access
Power and ground cable installation
Power wiring (External battery - PDP)
System cabling and final assembly
....................................................................................................................................................................................................................................
4 - 6