If additional grounding connections are wanted (or required), you
can do the following:
............................................................................................................................................................
1
Connect the office grounding cable — CC848834974 (item 1) to the
top of the rack-frame using two hexagonal M8 bolts and nuts as
shown in the figure below.
............................................................................................................................................................
2
Ground the PDP, the subracks, and all units which are also mounted
in the rack as shown in the figure below. The following ground cables
can be ordered:
•
Ground wire “PDP” 800 mm [2.625 ft] —
CC848828158 (item 2)
•
Ground wire “upper subrack” 2000 mm [6.562 ft] —
CC848828174 (item 3)
•
Ground wire “lower subrack” 3000 mm [9.843 ft] —
CC848828182 (item 3).
Result
Figure 4-11 Office and subrack grounding
Power and ground cable installation
Ground wiring
System cabling and final assembly
....................................................................................................................................................................................................................................
4 - 1 8