2200
86.615”
Rack dimensions
The racks require an area of 600 mm [23.622”] x 600 mm [23.622”]
(width x depth). This area represents the absolute system limits which
must not be exceeded in the operating state by protruding elements
such as switches or plugs. The standard height is 2200 mm [86.614”]
for an ETSI-2 rack and 2145 mm [84.448”] for an NEBS-2000 rack.
The racks are designed to accommodate two LambdaUnite
™
MSS
subracks.
Rack weights
The ETSI-2 rack has a maximum weight of 120 kg/264.6 lbs
(including PDP, cables and doors).
The NEBS-2000 rack has a maximum weight of 116 kg/255.8 lbs
(including PDP, cables and doors).
Subrack weight
The subracks have a maximum weight of 41 kg/90.41 lbs (including
user panel, fan, PIs, CI-CTL, TIs and 12x blanks at the rear).
Power consumption
The LambdaUnite MSS system has a maximum power consumption
of 3500 W.
EMC/ESD information
The system was developed in compliance with the ETSI Mesh Ground
requirements. This means EMC compliance and personnel safety can
be achieved only if the system is connected to a System-Reference
Potential Plane (SRPP) at many places as described in ETS 300 253
(see the figure below).
Important facts to know
General information
....................................................................................................................................................................................................................................
2 - 4
Lucent Technologies
365-374-074
Issue a, April 2002