Power wiring (PDP - PI/100)
....................................................................................................................................................................................................................................
Before you begin
This section can be skipped, if PI units are used (see section
).
Important! The PI/100 unit can only be used when the rack is
provided with 25mm
2
power cables.
PI/100 cables
Important! The cables are prefabricated and mounted within the rack
frames. Each cable (cable for side A and cable for side B) supports
both subracks (upper and lower).
The following PI/100 cables should be used within ETSI-2 racks:
•
PI/100 cable, A-side — CC848850723
•
PI/100 cable, B-side — CC848850715.
The following PI/100 cables should be used within NEBS-2000 racks:
•
PI/100 cable, A-side — CC848850749
•
PI/100 cable, B-side — CC848850731.
Legend:
4, 5
PI/100 cables (combined: yellow/green, red,
blue)
+DC (rtn)
red
Figure 4-7 PDP connection (PI/100 cables)
+DC (rtn)
(A+B)
-DC
(A+B)
Ground (A+B)
4A
5A
Power and ground cable installation
System cabling and final assembly
....................................................................................................................................................................................................................................
4 - 1 2
Lucent Technologies
365-374-074
Issue a, April 2002