Alarm reporting test
....................................................................................................................................................................................................................................
Overview
This test verifies that currently active alarms of the system are
reported to the WaveStar
®
CIT and the user panel. The test includes
raise and clear behaviour of the alarms created.
Related information
All the needed information for the tasks described below (creating and
clearing of alarms) is given in the “ LambdaUnite
™
MultiService
Switch (MSS) User Operations Guide”.
Procedure
Proceed as follows to complete the alarm test:
............................................................................................................................................................
1
Login to the NE as described in Chapter 6, section
............................................................................................................................................................
2
Create the different alarms in sequence as shown in the table below.
Example:
Create the following alarms separately:
Created alarm
Alarm level
Example for creation of
the alarm
Protection
Clock Input
Fail
Deferred/
Minor
Remove the XC320 circuit
pack which is located in the
protection slot 10.
NE Clock
Failure
Prompt/
Critical
Remove both XC320 circuit
packs (worker and
protection).
Stand alone test procedures
....................................................................................................................................................................................................................................
7 - 4
Lucent Technologies
365-374-074
Issue a, April 2002