Spare Parts and Replacement Procedures 8 - 15
4. During reinstallation, before attaching the clamp to the
frame, make sure that the bottom of the clamp is flush with
the bottom of the capacitor.
Diode Heat Sink
Assembly
It is possible to remove individual rectifier diodes from the heat
sink while the heat sink assembly is still mounted in the rectifier.
Any diode can be reached with a standard offset ratchet wrench
in this manner. However, the diode heat sink assembly can be
removed, if desired. It is easily dismounted from the rear of the
rectifier by loosening the bolts in the slotted brackets and then
lifting up and out. However, difficulty may be encountered in
getting the heat sink past some of the wires and cables that block
it from coming straight out, if the wires and cables are not
disconnected. The transformer leads should not be moved or
bent at their breakout points.
For diode testing or removal information, see “Rectifier Diode
Test and/or Replacement” later in this section.
DC Inductors
(L3 or L4)
Inductor L4, if equipped, is mounted just to the right of inductor
L3.
To Remove Inductor L3:
1. To access L3, remove the cable from the positive side
(left) of TB3. As shown in Figure 5-3, this is either Cable
A (in a negative output system) or Cable B (in a positive
output system).
2. Disconnect the lead from the inner tab of L3.
3. Remove the other (outer tab) lead (coming from L3) from
its connection point at the junction of leads 7 of T1 and T2
(near the bottom of the rectifier in the middle). This
requires removing the tape and unbolting the connection
terminals of the 1/0 gauge leads.
4. While supporting the weight of L3, remove all four of the
mounting nuts that secure it to the rear wall. Remove L3.
To Remove Inductor L4:
1. Remove the CBA1 bracket assembly as described in “DC