8 - 8 Spare Parts and Replacement Procedures
Issue 6 October 1998
10. Plug in the cable connector that leads to the control board.
11. Check calibration of rectifier meter as described in “Meter
Calibration Test (Off Line)” in Section 6, Testing.
12. If the rectifier is to be restored to service, refer to “Restore
Rectifier to Service” in Section 7, Troubleshooting and
Adjustments.
General
Considerations
for Replacing
Components
Only disassembly procedures are given in this section.
Reinstallation procedures are usually the exact reverse of
removal procedures (i.e., follow the removal procedures in
reverse to reinstall the component). Specific instructions are
given when this does not apply exactly, or where special
considerations or precautions must be taken during
reinstallation. Applicable portions of Section 5, Installation,
may be helpful. Portions of Section 6, Testing, can be used after
reinstallation to verify proper operation of the rectifier. Some
points are common to all rectifier disassembly work. Please read
this section before using the rectifier disassembly procedures.
•
Take precautions against accidental personal injury or
damage to equipment. Observe warnings given in Section
2, Product Description, in addition to the following
admonishment, while undertaking any disassembly or
reinstallation procedure on a rectifier.
The ac service and dc battery buses can be safely
disconnected from the rectifier by following the first eight
steps of “Disconnecting a Rectifier” later in this section,
but all work must be done carefully because you are
working with live cables at battery bus potentials and
current capabilities. The disconnected charge battery and
charge ground connectors must be taped adequately to
DANGER
The following disassembly or reinstallation procedures
MUST be performed only on a rectifier completely
disconnected from the plant battery buses, AND with no input
from the ac service panel connected to the rectifier. The plant
control cable J2A should also be disconnected from the CM2
board.