Equipment and Cable Installation for Metropolis
®
DMXplore Shelf (Rack-Mount)
Power Cable Installation
...........................................................................................................................................................................................................................................................
2 - 1 5
365-372-334 R2.0
Issue 4, November 2004
torque screwdriver set to 0.5 Nm (4.4 lb-in) to tighten. See Figure 2-7,
Power Connection (page 2-15).
Important!
Power cables must be between 12 AWG and 20 AWG
and have an 8mm wire strip length for connection to the terminal
block. Use the guide located on the inside of the cover on the lower
right hand for accurate lengths.
Figure 2-7
Power Connection
Table 2-4
Power Cable Color Coding
...........................................................................................................................................................................
Step 3
Route the power cables toward the power source (e.g. AC/DC
Converter, BDCBB, BDFB etc.)
Important!
The Metropolis
®
DMXplore is powered by -48 V DC.
CAUTION
If using BBCBB or BDFB, verify that the BDCBB breakers are
off or that the BDFB fuses are not installed.
Color Coding
Connection
Red
-48V-A
Red/Black
RTN-A
Blue
-48V-B
Blue/Black
RTN-B
Summary of Contents for Metropolis DMXplore
Page 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Page 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Page 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Page 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Page 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...