Installation Tests
Local Equipment and Cross-connect Tests
...........................................................................................................................................................................................................................................................
6 - 9
365-372-334 R2.0
Issue 4, November 2004
............................................................................................................................................................................................................................................................
Local Equipment and Cross-connect Tests
Description
The tests in this section verify the proper operation of the circuit packs
and the circuit pack positions in the Metropolis
®
DMXplore shelf. It
verifies proper cabling from the Metropolis
®
DMXplore to the access
panel or connecting equipment. The shelf must successfully pass this
test before testing any other feature of the Metropolis
®
DMXplore.
It is assumed that Chapter 3, Powering and Initial Circuit Pack
Installation for Metropolis
®
DMXplore Shelf (Wall-Mount) or Chapter
4, Powering and Initial Circuit Pack Installation for Metropolis
®
DMXplore Shelf (Rack-Mount) is complete and the Metropolis
®
DMXplore shelf has fiber loopback cables on the Main OLIUs, with
far-end communication (see ent-fecom TL1 command) parameter
disabled and synchronization set to free-running.
On initial installation/turn-up of Metropolis
®
DMXplore there are
default cross-connects. No cross-connects will need to be entered for
these tests.
Important!
After completing this test, isolate and correct any
incorrect wiring or isolate and replace any failed units. If any
cabling is corrected or units replaced, repeat the Local Equipment
and cross-connect tests until the units pass without failures.
CAUTION
...........................................................................................................................................................................
A properly grounded ESD wrist strap MUST be worn when
handling circuit packs.
WARNING
Unterminated optical connectors may emit laser radiation. Do
not view beam with optical instruments.
Summary of Contents for Metropolis DMXplore
Page 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Page 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Page 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Page 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Page 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...