Operational Tests
Miscellaneous (Environmental) Discrete
Telemetry Test
...........................................................................................................................................................................................................................................................
7 - 1 7
365-372-334 R2.0
Issue 4, November 2004
...........................................................................................................................................................................
Step 4
Click on the
opr-ext-cont
command. Under the
<OPREXTAID>
double click on
{1}
and select control output to operate.
...........................................................................................................................................................................
Step 5
Click
Send
to issue the command.
Result:
The Response Window will display the command followed
by a
COMPLD
indication as well as indicating the correct control
output has been activated.
...........................................................................................................................................................................
Step 6
Verify the correct control output was operated (e.g. generator, pump,
etc.).
...........................................................................................................................................................................
Step 7
Click on the
rtrv-ext-cont
command. Under the
<CONTROLAIDRTRV>
double click on
{all}
and select control output
to retrieve.
...........................................................................................................................................................................
Step 8
Click
Send
to issue the command.
...........................................................................................................................................................................
Step 9
Click on the
rls-ext-cont
command. Under the
<OPREXTAID>
double
click on
{1}
and select control output to release.
...........................................................................................................................................................................
Step 10
Click
Send
to issue the command.
Result:
The Response Window will display the command followed
by a
COMPLD
indication as well as indicating the correct control
output has been released.
Repeat Step 3 through Step 8 for each environmental input being
used.
...........................................................................................................................................................................
Step 11
Check off the appropriate box in Appendix E, Installation Checklist.
End of Steps
...........................................................................................................................................................................
Summary of Contents for Metropolis DMXplore
Page 8: ... C O N T E N T S v i i i 365 372 334 R2 0 Issue 4 November 2004 ...
Page 16: ... T A B L E S x v i 365 372 334 R2 0 Issue 4 Novmeber 2004 Glossary ...
Page 286: ... Backplane Pin Replacement Replacement Methods D 1 0 365 372 334 R2 0 Issue 4 November 2004 ...
Page 292: ... Installation Checklist Overview E 6 365 372 334 R2 0 Issue 4 November 2004 ...
Page 326: ... G L O S S A R Y G L 3 0 365 372 334 R2 0 Issue 4 November 2004 ...