Equipment and Cable Installation for Metropolis
®
DMXplore Shelf (Wall-Mount)
Miscellaneous (Environmental) Discrete
Telemetry Cable Installation
1 - 4 0
365-372-334 R2.0
Issue 4, November 2004
Figure 1-17 Miscellaneous Discretes and Office Alarm Cable
Routing
...........................................................................................................................................................................
Step 3
Cut the miscellaneous (environmental) discrete telemetry cable to the
desired length at the telemetry panel.
...........................................................................................................................................................................
Step 4
Wire-wrap the loose end of the miscellaneous (environmental) discrete
telemetry cable to the wire-wrap terminal strip, making connections per
Table 1-12, Miscellaneous (Environmental) Discrete Telemetry
Connections (page 1-38).
Important!
Each miscellaneous (environmental) discrete
telemetry designation is connected to the Metropolis
®
DMXplore
by two leads (wires). For each input, one lead should be connected
to input-common and the other lead should be connected to the
appropriate alarm indication. For each output, one lead should be
connected to output-common and the other lead should be
connected to the appropriate alarm indication.
...........................................................................................................................................................................
Step 5
Check off the appropriate box in Appendix E, Installation Checklist.
End of Steps
...........................................................................................................................................................................