Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
Miscellaneous (Environmental) Discrete
Telemetry Cable Installation
...........................................................................................................................................................................................................................................................
1 - 7 3
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 2
Route the cable out of the Metropolis
®
DMXtend bay per Figure 1-26,
Miscellaneous Discrete Cable Routing (page 1-73) to the telemetry
panel.
Figure 1-26 Miscellaneous Discrete Cable Routing
............................................................................................................................................................................
Step 3
Cut the miscellaneous (environmental) discrete telemetry cable to the
desired length at the telemetry panel.
............................................................................................................................................................................
Step 4
Wire-wrap the loose end of the miscellaneous (environmental) discrete
telemetry cable to the wire-wrap terminal strip, making connections per
Table 1-27, Miscellaneous (Environmental) Discrete Telemetry
Connections (page 1-75).
Important!
Each miscellaneous (environmental) discrete
telemetry designation is connected to the Metropolis
®
DMXtend by
two leads (wires).
For each input, one lead should be connected to input-common and
the other lead should be connected to the appropriate alarm
indication.
For each output, one lead should be connected to output-common
and the other lead should be connected to the appropriate alarm
indication.