Powering and Initial Circuit Pack Installation for
Metropolis
®
DMXtend Shelf Horizontal Bay Mount
Powering
2 - 6
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 15
At the BDFB either insert the fuse or put the circuit breaker, associated
with the “A” feed of the Metropolis
®
DMXtend, in the ON position.
............................................................................................................................................................................
Step 16
Verify that the both the PWR A LED and PWR B LED on the
Metropolis
®
DMXtend user panel are lighted with both the “A” and
“B” feeds powered.
............................................................................................................................................................................
Step 17
Verify that the fans are still running and are moving air.
............................................................................................................................................................................
Step 18
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps