Operational Tests
Office Alarm Test
...........................................................................................................................................................................................................................................................
5 - 7
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 8
Click
Send
to issue the command.
Result:
The Response Window should display the command
followed by a
COMPLD
indication.
............................................................................................................................................................................
Step 9
Use the scroll bar in the
Command Builder
window to scroll down to
the
rtrv-crs-sts1
command.
............................................................................................................................................................................
Step 10
Click on the
rtrv-crs-sts1
command.
............................................................................................................................................................................
Step 11
Click
Send
to issue the command.
Result:
The Response Window should display the command
followed by a
COMPLD
indication as well as displaying the cross-
connect that was just entered.
............................................................................................................................................................................
Step 12
Unseat one of the LNW6/LNW7 (28DS1), LNW16 (12DS3/EC1) or
LNW39 (DS1/DS3/16/3) circuit packs from the function group being
used.
Requirement:
Activated office alarms:
MN
visual, MN audible.
Important!
Alarms will not be activated until the alarm delay time
has passed. The default time is 2 seconds.
............................................................................................................................................................................
Step 13
Press the
ACO
pushbutton on the SYSCTL.
Requirement:
Activated office alarm:
MN
visual.
The MN audible alarm clears.
............................................................................................................................................................................
Step 14
Disconnect one of the optical fiber jumpers from the
OUT
port of the
OLIU circuit pack in the
M1
slot.
Requirement:
Activated office alarms:
MJ
visual, MJ audible.