Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
Metropolis
®
DMXtend Shelf Installation
1 - 1 2
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 7
Determine the position that the Metropolis
®
DMXtend shelf will be
mounted. Start at the bottom of the bay and add shelves from bottom to
top.
Important!
If a fiber duct is being used to diversify fiber, a 1 in.
space is required to accommodate the duct below the existing
Metropolis
®
DMXtend. Use the Assembly Fiber Duct kit drawing
848949152 to attach the duct to the Metropolis
®
DMXtend See
Figure 1-3, Fiber duct mounting (page 1-12)
Important!
If the Metropolis
®
DMXtend shelf is to be installed
above or below existing equipment that does not have a heat baffle,
then a heat baffle (C 848862181) must be installed between the
shelf and the existing equipment.
Important!
If there is space left in the bayframe above the last
Metropolis
®
DMXtend shelf installed a heat baffle must be installed
above the shelf to prevent accidental damage to the power cables at
the top of the shelf.
Figure 1-3
Fiber duct mounting
............................................................................................................................................................................
Step 8
Position the Metropolis
®
DMXtend shelf in the frame and secure the
shelf to the frame using the thread-forming screws included with the
shelf (3 screws per side). Tighten the screws to 21 in.-lb. (minimum)/30
in.-lb. (maximum)
Important!