Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
TL1/X.25 Interface Cable Installation
...........................................................................................................................................................................................................................................................
1 - 6 1
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Table 1-20
X.25-AISW Interface Connections
Conn.
Metropolis
®
DMXtend
Bkpl
Color
AISW
Conn.
Designation
Name
J19
2
BL
3
TDA
Transmitted Data
3
O
2
RDA
Received Data
4
W-BL
5
RTS
Request to Send
5
G
4
CTS
Clear to Send
6
See Note 1
6
DSR
Data Set/DCE Ready
7
S
7
GRD
Signal Ground
8
R
20
DCD
Received Line Signal Detector
15
W
17
TCK
Transmitter Signal Element
Timing
17
BK
15
RCK
Receiver Signal Element Timing
20
Y
8
DTR
Data Terminal/DTE Ready
22
V
22
RID
Ring Indicator
Notes:
1. Pins# 6 and 8 are connected through a 26 gauge DP3 wire or equivalent.
Table 1-21
X.25-X.25 Interface Connections
Conn.
Pin#
Color
Designation
Name
J19
2
BL
TDA
Transmitted Data
3
O
RDA
Received Data
4
G
RTS
Request to Send
5
W-BL
CTS
Clear to Send
6
BR
DSR
Data Set/DCE Ready
7
S
GRD
Signal Ground
8
Y
CDC
Received Line Signal Detector
15
BK
TCK
Transmitter Signal Element Timing
17
W
RCK
Receiver Signal Element Timing
20
R
DTR
Data Terminal/DTE Ready
22
V
RID
Ring Indicator