Equipment and Cable Installation for Metropolis
®
DMXtend
Shelf Horizontal Bay Mount
Office Alarm Cable Installation
...........................................................................................................................................................................................................................................................
1 - 7 1
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Table 1-25
Office Alarm Connections
Conn.
Pin#
Color
Designation
Name
J13-J14
1
2
3
4
BL-W
W-BL
O-W
W-O
RYMJV1
RYMJV2
RYMJA1
RYMJA2
Major Alarm Visible
Major Alarm Visible Return
Major Alarm Audible
Major Alarm Audible Return
5
6
7
8
G-W
W-G
BR-W
W-BR
RYMNV1
RYMNV2
RYMNA1
RYMNA2
Minor Alarm Visible
Minor Alarm Visible Return
Minor Alarm Audible
Minor Alarm Audible Return
9
10
11
12
S-W
W-S
BL-R
R-BL
RYCRV1
RYCRV2
RYCRA1
RYCRA2
Critical Alarm Visible
Critical Alarm Visible Return
Critical Alarm Audible
Critical Alarm Audible Return
Notes:
1. The SYSCTL circuit pack reports office alarms.
2. The connection to the central office alarms from P13 is run for each Metropolis
®
DMXtend shelf assembly when used in a miscellaneously mounted individual
application or from the first Metropolis
®
DMXtend shelf assembly when mounted in a
typical bay arrangement.