Powering and Initial Circuit Pack Installation for
Metropolis
®
DMXtend Shelf Horizontal Bay Mount
Initial Circuit Pack Installation
...........................................................................................................................................................................................................................................................
2 - 1 3
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 3
Place the SYSCTL circuit pack into the
CTL
slot on the Metropolis
®
DMXtend shelf. Do NOT engage the circuit pack in the backplane
connector.
............................................................................................................................................................................
Step 4
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps
OC-3/OC-12 Main OLIU
Installation
Follow this procedure to install the following OC-3/OC-12 Main OLIU
circuit packs in the Metropolis
®
DMXtend shelf.
•
LNW40 OC-3 IR
•
LNW38 OC-12 IR
•
LNW51 OC-12 LR (Supported in Release 1.1)
Step 1
Remove the first Main OLIU circuit pack from the packing material.
............................................................................................................................................................................
Step 2
Identify the
M1
slot on the Metropolis
®
DMXtend shelf. See
Figure 2-2, Metropolis® DMXtend Shelf (page 2-10).
............................................................................................................................................................................
Step 3
Place the Main OLIU circuit pack into the
M1
slot on the Metropolis
®
DMXtend shelf. Do NOT engage the circuit pack in the backplane
connector.
............................................................................................................................................................................
Step 4
Remove the second Main OLIU from the packing material.
............................................................................................................................................................................
Step 5
Identify the
M2
slot on the Metropolis
®
DMXtend shelf. See
Figure 2-2, Metropolis® DMXtend Shelf (page 2-10).
............................................................................................................................................................................
Step 6
Place the second Main OLIU circuit pack into the
M2
slot on the
Metropolis
®
DMXtend shelf. Do NOT engage the circuit pack in the
backplane connector.