Powering and Initial Circuit Pack Installation for
Metropolis
®
DMXtend Shelf Horizontal Bay Mount
Initial Circuit Pack Installation
2 - 1 4
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Important!
If any of the Main slots are to remain unequipped, install
a LNW42 or LNW95(R1.1) apparatus blank to provide proper air flow
for cooling.
............................................................................................................................................................................
Step 7
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps
LNW39(DS1/DS3/16/
3)LNW111(3DS3) and
LNW112(16DS1) Low
Speed Installation
(Optional)
Follow this procedure only if installing LNW39(DS1/DS3/16/3),
LNW111(3DS3), or LNW112(16DS1) circuit packs into the
Metropolis
®
DMXtend shelf.
Step 1
Refer to the engineering job specification. Identify the proper function
group slots that LNW39(DS1/DS3/16/3), LNW111(3DS3), or
LNW112(16DS1) circuit pack will be installed into.
............................................................................................................................................................................
Step 2
Remove the LNW39(DS1/DS3/16/3),LNW111(3DS3), or
LNW112(16DS1) from the packing material.
............................................................................................................................................................................
Step 3
Place the circuit pack into the shelf (slot A1/B1). Do NOT engage the
circuit pack in the backplane connector.
............................................................................................................................................................................
Step 4
If a protection circuit pack is required, continue with Step 5 If not,
install a LNW43 or LNW96(R1.1) Apparatus Blank into the protection
circuit pack slot (A2/B2), then proceed to Step 7.
Important!
LNW43 or LNW96(R1.1)Apparatus Blanks are required
in all unused slots A1/B1 and A2/B2 to provide proper air flow for
cooling.
............................................................................................................................................................................
Step 5
Remove the second LNW39(DS1/DS3/16/3), LNW111(3DS3), or
LNW112(16DS1) from the packing material.
............................................................................................................................................................................
Step 6
Place the circuit pack into the shelf (slot A2/B2). Do NOT engage the
circuit pack in the backplane connector.