Powering and Initial Circuit Pack Installation for
Metropolis
®
DMXtend Shelf Horizontal Bay Mount
Initial Circuit Pack Installation
2 - 2 4
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
Step 1
Refer to the engineering job specification. Identify the proper function
group slot (D1 or G1) where the LNW68 (1G LX)(R1.1) circuit pack
will be installed.
Important!
LNW68 (1G LX)(R1.1) circuit pack can only be
installed in slot 1 of any function group.
............................................................................................................................................................................
Step 2
Remove the LNW68 (1G LX)(R1.1) from the packing material.
............................................................................................................................................................................
Step 3
Place the circuit pack into the shelf (slot D1 or G1 as required). Do
NOT engage the circuit pack in the backplane connector.
............................................................................................................................................................................
Step 4
Install a 177D or LNW98 Apparatus Blank into the companion circuit
pack slot (D2 or G2 as required).
Important!
177D or LNW98 Apparatus Blanks are required in all
unused slots D and G to provide proper air flow for cooling.
............................................................................................................................................................................
Step 5
Repeat Step 1 through Step 4 for each additional function group to be
equipped with LNW68 (1G LX)(R1.1) circuit packs.
............................................................................................................................................................................
Step 6
Check off the appropriate box in Appendix E, Installation Checklist.
...........................................................................................................................................................................
End of Steps
177D, LNW98 Apparatus
Blank Installation
(Optional)
Follow this procedure to install 177D or LNW98 Apparatus Blank(s)
into the Metropolis
®
DMXtend shelf.
Important!
177D or LNW98 Apparatus Blanks are required in all
unused slots D and G to provide proper air flow for cooling.
Step 1
Identify all the unequipped Function Unit (D or G) slots.
............................................................................................................................................................................
Step 2
Remove the 177D or LNW98 Apparatus Blank from the packing
material.