Installation Tests
Local Equipment and Cross-connect Tests
...........................................................................................................................................................................................................................................................
4 - 2 3
Lucent Technologies - Proprietary
See notice on first page
365-372-327 R2.0
Issue 1, October 2003
............................................................................................................................................................................
Step 11
Click on the
canc-user
command to log out of the Network Element.
............................................................................................................................................................................
Step 12
Click
Send
to issue the command.
............................................................................................................................................................................
Step 13
At the RJ45 Ethernet patch panel disconnect the RJ45 Ethernet cable
run to the PC Ethernet port and connect it to the next position on the
RJ45 Ethernet patch panel to be tested.
............................................................................................................................................................................
Step 14
Ignore the flashing fault LED on the LNW71 (10/100-PL), or LNW66
(10/100T) (R1.1) and any alarms on the shelf.
............................................................................................................................................................................
Step 15
Watch for the link LED to light on the PC’s Ethernet card or wait for 30
seconds.
............................................................................................................................................................................
Step 16
Click on the
act-user
command to log in to the Network Element
............................................................................................................................................................................
Step 17
Click
Send
to issue the command.
............................................................................................................................................................................
Step 18
Wait for the login banner to be displayed in the Response Window.
............................................................................................................................................................................
Step 19
Click on the
canc-user
command to log out of the Network Element.
............................................................................................................................................................................
Step 20
Click
Send
to issue the command.
............................................................................................................................................................................
Step 21
Repeat this procedure starting at Step 10 for the remaining Ethernet
connections on RJ45 patch panel connected to the LNW71 (10/100-
PL), or LNW66 (10/100T) (R1.1) under test, then continue on to Step
22
............................................................................................................................................................................
Step 22
Close the command builder window and disconnect the PC from the
RJ45 patch panel and the Metropolis
®
DMXtend LAN port from the
RJ45 patch panel.
............................................................................................................................................................................
Step 23
Connect the Front CIT cable between the PC and the CIT/RS 232 jack
of System Controller and login to the shelf using the serial connection
and the TL1/Command Builder options on WaveStar